Evaluate door station voice message
Contents

1.Description

This module is used in conjunction with the DCS IP gateway (Gira Order No. 2620 ..).
It evaluates whether a voice message on a door station by the Gira HomeServer (logic node: Send/Door station voice message) is confirmed by the DCS IP gateway.

Input 2 (bus address) acts here as a filter, i.e., only telegrams are evaluated which match the filter properties.
If successful, the module at Output 1 sends a 1 telegram.
In the case of an error, Output 1 sends a 0 telegram.
Note
The module requires the firmware version of the DCS IP gateway 3 or higher!

2.Inputs

No.NameInitialisationDescription
1Door communication Receive""
(14 bytes – Text)
Here the internal communication object Door communication Receive is assigned by the DCS IP gateway.
2Bus address""
(14 bytes – Text)

Optional specification of a bus address to which filtering should be applied.
The bus address must have the following format:
Example: 0xABCD07 or 0x42A305
Note
If this input remains free, the telegrams of random bus addresses are evaluated.
If a communication object is assigned but is not written to or provided with an initialisation value, then the object is considered not to be set. This means the incoming telegrams of all bus addresses are evaluated.

3.Outputs

No.NameInitialisationSBCDescription
1Voice message successful0s
(1 Bit)
The voice message triggered on the door station via the Gira HomeServer logic node is confirmed with a 1-telegram if successful. In the case of an error a 0-telegram is sent.
2Bus address""s
(14 bytes – Text)
Output of the bus address in the format: 0xABEF07
3Current status0s
(-255 to 255)
The output sends the current status of the voice message.

0 = The voice message(s) are played
1 = The voice message(s) was/were played back successfully. The conversation has ended.

-1 = The door station does not respond
-2 = Voice message cancelled because of external event
-3 = The max. playback time (max. 2 min) was exceeded by the total voice messages
-4 = The voice message ID is unknown
4Number of unknown voice message ID0s
(1 byte: 0-255)
The output provides the number of the unknown voice message ID (value range 0 to 255).
5Error output0s
(1 byte: 0-255)
The output can be routed to the outside as a diagnostic output if necessary or during start-up in order to obtain information about possible errors.
Values in the value range of 0 to 3 are sent.

0 = An error has not occurred.
1 = Check the length of the bus address
2 = Check the characters of the bus address
3 = A telegram with another structure was received.
s = send, sbc = send by change

4.Other

Recalculation during start:No
Module is retentive:No
Internal designation:16941
Category:Door communication\Receive

5.Similar functions

Receive
Receive\Evaluate code from code keypad
Send
Additional modules