7x universal value comparator
Contents

1.Description

The module is specially matched to the logic nodes in the area of door communication for the Gira DCS-IP gateway (Article No. 2620xx).
The module is suitable for the comparison of values with default values (e.g. sender types, Keyless In device types or index numbers).
If a comparison is correct, then the related output is set to the value 1.
If the value does not match any specification, then, for example, an entry can be made in a message archive.

If a telegram is received at Input 1, then all 7 comparison values are compared consecutively with the value (Input 1).
If one of the comparison values matches the value at Input 1, then a 1 is sent to the related output and the comparison is cancelled.
If no value matches, then Output 8 sends a 1 telegram. Telegrams to Inputs 2-8 do not cause a calculation of the module.

2.Inputs

No.NameInitialisationDescription
1Input value0
This input receives the variable value with which the 7 comparison values are compared.
2Comparison value 1-1
Value to be compared.
3Comparison value 2-1
Value to be compared.
4Comparison value 3-1
Value to be compared.
5Comparison value 4-1
Value to be compared.
6Comparison value 5-1
Value to be compared.
7Comparison value 6-1
Value to be compared.
8Comparison value 7-1
Value to be compared.

3.Outputs

No.NameInitialisationSBCDescription
1Trigger for comparison value 10s
The output sends a 1 when the value received at Input 1 matches the value at Input 2.
2Trigger for comparison value 20s
The output sends a 1 when the value received at Input 1 matches the value at Input 3.
3Trigger for comparison value 30s
The output sends a 1 when the value received at Input 1 matches the value at Input 4.
4Trigger for comparison value 40s
The output sends a 1 when the value received at Input 1 matches the value at Input 5.
5Trigger for comparison value 50s
The output sends a 1 when the value received at Input 1 matches the value at Input 6.
6Trigger for comparison value 60s
The output sends a 1 when the value received at Input 1 matches the value at Input 7.
7Trigger for comparison value 70s
The output sends a 1 when the value received at Input 1 matches the value at Input 8.
8Other case0s
If the value received at Input 1 does not match any of the comparison values, then the output sends a 1.
s = send, sbc = send by change

4.Other

Recalculation during start:No
Module is retentive:No
Internal designation:16938
Category:Door communication\Additional modules

5.Similar functions

Receive
Receive\Evaluate code from code keypad
Send
Additional modules