1.Description
This module is used in conjunction with the DCS IP gateway (Gira Article No. 2620xx). As a result, sabotage on the Gira Keyless In units or the control device can be evaluated and functions can be run in the HS/FS or KNX.
With the optional assignment of the Inputs 2 to 5, the arriving telegrams can be filtered with regard to the following properties:
- Bus addresses
- Gira Keyless In device types
- Sender type
- Target address
This means that: With inputs set, only telegrams (with switching actions and sabotage information) are evaluated which match the filter properties. Here it is irrelevant whether one or more inputs are assigned.
Examples:
With the bus address "0xABCDEF" set, only sabotage telegrams are evaluated which have been sent from the bus address "0xABCDEF".
By setting the Gira Keyless In device type to the value "Fingerprint", all sabotage telegrams from the fingerprint reader are evaluated which contain a TC bus switching action, regardless of the sender or the bus address.
With the bus address "0xABCDEF" set, only sabotage telegrams are evaluated which have been sent from the bus address "0xABCDEF".
By setting the Gira Keyless In device type to the value "Fingerprint", all sabotage telegrams from the fingerprint reader are evaluated which contain a TC bus switching action, regardless of the sender or the bus address.
Note
If no filters are set, then all sabotage telegrams of code keypads or fingerprint readers will be evaluated!
Determination of the optional filter parameters
Two different methods are available for determining the filter parameters:
Two different methods are available for determining the filter parameters:
- Use of the HomeServer cheat sheet in the DCS IP gateway.
- Use of the logic node Display basic parameters in the "Door communication\Additional nodes" folder.
After the parameters are known, it is recommended that the inputs be assigned either group addresses or fixed values.
2.Inputs
No. | Name | Initialisation | Description |
---|---|---|---|
1 | Door communication Receive | "" | (14 bytes – Text) Here the internal communication object Door communication Receive is assigned by the DCS IP gateway. |
2 | Bus address | "" | (14 bytes – Text) Optional specification of a bus address to which filtering should be applied. The bus address must have the following format: Example: 0xABCD07 or 0x42A305 Note If this input remains free, the telegrams of random bus addresses are evaluated. If a communication object is assigned but is not written to or provided with an initialisation value, then the object is considered not to be set. This means the incoming telegrams of all bus addresses are evaluated. |
3 | Gira Keyless In device type | 0 | (Value range 0 to 7) 0 = Control device or Keyless In units 1 = Transponder reader 2 = Fingerprint reader 3 = Code keypad |
4 | Sender type | 0 | Optional specification of a sender type to which filtering should be applied. The following parameters are possible: 160 = Door station 161 = Living area intercom 162 = Living area intercom receiver 163 = Bus control device 164 = Switching actuator 165 = TC gateway 166 = Additional gong/Bus chiming mechanism 167 = Button interface 168 = DCS IP gateway |
5 | Target address | "0x000010" | Optional specification of a target address to which filtering should be applied. The target address must have the following format here: Examples: 0xABCD07 or 0x42A305 Note If the initialisation value remains unchanged, then the telegrams of any desired target addresses will be evaluated. If a communication object is assigned but is not written to or provided with an initialisation value, then the object is considered not to be set. This means the arriving telegrams of all target addresses are evaluated. |
3.Outputs
No. | Name | Initialisation | SBC | Description |
---|---|---|---|---|
1 | Sabotage | 0 | s | A 1 is sent on this output when the sabotage input telegram matches all filter properties. If filters are missing, then a 1 is sent each time a sabotage message is received. For input telegrams which do not meet the filter criteria, the output sends a 0. |
2 | Bus address | "" | s | (14 bytes – Text) Output of the bus address in the format: Gira 0xABEF07 |
3 | Gira Keyless In device type | 0 | s | (Value range 0 to 7) 0 = Control device 1 = Transponder reader 2 = Fingerprint reader 3 = Code keypad |
4 | Sender type | 0 | s | Device type from which the TC bus telegram has been sent. 160 = Door station 161 = Living area intercom 162 = Living area intercom receiver 163 = Bus control device 164 = Switching actuator 165 = TC gateway 166 = Additional gong/Bus chiming mechanism 167 = Button interface 168 = DCS IP gateway |
5 | Target address | "" | s | (14 bytes – Text) Output of the target address in the format: 0xABEF07 |
6 | Error output | 0 | s | The output can be routed to the outside as a diagnostic output if necessary or during start-up in order to obtain information about possible errors. Values in the value range 0 to 5 are sent. 0 = An error has not occurred. 1 = The default values must be checked. 2 = The characters of the bus or target address must be checked. 3 = A telegram with a different structure has been received (e.g. a light call). 4 = The logic is blocked. |
s = send, sbc = send by change
4.Other
Recalculation during start: | No |
---|---|
Module is retentive: | No |
Internal designation: | 16931 |
Category: | Door communication\Receive |
5.Similar functions
Receive
Switching action
Floor call
Internal call
Door call (incl. bell symbol on code keypad)
Switching action Gira Keyless In
Door opener command
Door opener command of device with Gira Keyless In
Light function
Evaluate status automatic door opener DCS Communicator
Button event DCS Communicator
Button event home station/TC gateway
Evaluate voice message door station
Evaluate status of forwarding
Response - Evaluate status of JPEG image call
Evaluation of sabotage control device
Floor call
Internal call
Door call (incl. bell symbol on code keypad)
Switching action Gira Keyless In
Door opener command
Door opener command of device with Gira Keyless In
Light function
Evaluate status automatic door opener DCS Communicator
Button event DCS Communicator
Button event home station/TC gateway
Evaluate voice message door station
Evaluate status of forwarding
Response - Evaluate status of JPEG image call
Evaluation of sabotage control device
Receive\Evaluate code from code keypad
Universal filter function with code specification as text
Universal filter function with code specification as value
Universal filter function with code specification as value
Send
Light function
Switching action
Query/set automatic door opener DCS Client
Door station voice message
Query/set forwarding
Terminate call status of DCS bus devices
Switching action
Query/set automatic door opener DCS Client
Door station voice message
Query/set forwarding
Terminate call status of DCS bus devices
Additional modules