1.Description
The "Scene" environment requires (per project) the following nodes:
- At least one 19994 master node (this node)
- At least one 19995 Scene node per Master node
The environment settings are made in the master. The scenes are managed by scene nodes.
The use of these nodes creates an accessible endpoint (a URL) on the HomeServer/FacilityServer through which scenes can be created, learned and retrieved. The communication objects used for this purpose must have special entries (Tags) so that they can be used in the scene environment. For more information, see the 19995 Scene Node documentation.
The use of these nodes creates an accessible endpoint (a URL) on the HomeServer/FacilityServer through which scenes can be created, learned and retrieved. The communication objects used for this purpose must have special entries (Tags) so that they can be used in the scene environment. For more information, see the 19995 Scene Node documentation.
Important
Note that with this node, all inputs can only be assigned their initial values or fixed values. It is not possible to connect communication objects to these inputs!
Note
It is strongly recommended to leave all input values at the default settings.
If default values are to be used for all inputs then for any input, the Init value (represented by a green background in the GLE) must be changed to a fixed value (represented by a yellow background in the GLE). This is necessary because the project can not be transferred until at least one input is assigned to each node.
Double-click on an input and confirm the suggested value. Now the input is shown with a yellow background, which means that a fixed value is set and the input is detected as "allocated".
If default values are to be used for all inputs then for any input, the Init value (represented by a green background in the GLE) must be changed to a fixed value (represented by a yellow background in the GLE). This is necessary because the project can not be transferred until at least one input is assigned to each node.
Double-click on an input and confirm the suggested value. Now the input is shown with a yellow background, which means that a fixed value is set and the input is detected as "allocated".
2.Inputs
No. | Name | Initialisation | Description |
---|---|---|---|
1 | Standard scene name | "Scene" | This text is the default name for all scenes. The scenes can be renamed manually at a later time. Default value: "Scene" Important Must be entered as a fixed value in the input! |
2 | Modules title | "Modules" | The text specified here will be used as the title of the Scene Environment start page. Default value: "Modules" Important Must be entered as a fixed value in the input! |
3 | Password | "" | A password must be specified! The first time you access the node's web interface, you must log in with this password. The password can then be changed via the interface. Default value: "" Important Only evaluated at system startup! |
4 | Basic path | "/scenes/" | The sub-path entered here (on the HS/FS) serves as the start page for the scene environment. Default value: "/scenes/" Example (for the default value): HTTPS://[IP-ADR]/scenes/ Important This path must start with a "/" (slash) and end with a "/" (slash)! This should also be considered when using the address in a browser! Must be entered as a fixed value in the input! When using more than one master node, do not use the same Base Path twice! |
5 | Port | 0 | The port specified here must not be changed. Default value: 0 Warning Leave initialisation value 0 set to the default value! Do not specify any fixed value! |
3.Outputs
No. | Name | Initialisation | SBC | Description |
---|---|---|---|---|
1 | Module ID | 0 | s | Must be connected to the same name input of all scene nodes (19995) managed by this master. |
s = send, sbc = send by change
4.Other
Recalculation during start: | Yes |
---|---|
Module is retentive: | Yes |
Internal designation: | 19994 |
Category: | Additional modules\Scenes |