Fan controller 3 speeds
Contents

1.Description

The module is used to control a 3-speed fan. The basic operation of the fan was modelled on the operation of air conditioning systems for vehicles.

Manual mode: Following release, the user can directly specify the fan speed (values 1-3 at Input 2) or can switch off the fan directly (1 signal at Input 5). In addition, it is possible to switch between the fan speeds 1-3 and Fan Off as desired via the inputs Speed + or Speed –.

Automatic mode: Automatic mode is activated via Input 6 and set to the specified fan speed via Input 7. When automatic mode is activated, a 1 signal on the inputs Speed –, Speed +, the input "Switch off" or the direct speed specification results in switching over to Manual mode. After another main release, the operating mode (speed) is active before the lock-out is active. To illustrate the processes, the module contains not only the 1-bit status outputs, but also a 1-byte output. The values sent via this output can be converted into fixed texts by means of comparators.

2.Inputs

No.NameInitialisationDescription
1Release0
Superordinate release (1 bit, 1 = released 0 = blocked)
2Direct selection of speed0
Value for direct speed specification (1 byte) Value 1 = Speed 1, Value 2 = Speed 2, Value 3 = Speed 3
3Speed +10
Speed + (1 bit), when a 1 signal is received, the speed is increased by 1 and the fan is switched to Manual mode if necessary.
4Speed 10
Speed - (1 bit), when a 1 signal is received, the speed is decreased by 1 and the fan is switched to Manual mode if necessary.
5Switch off0
Switch-off (1 bit), when a 1 signal is received, the fan is switched off and switched to Manual mode if necessary.
6Automatic0
Automatic (1 bit), when a 1 signal is received, the fan is switched to Automatic mode.
7Pre-selection of speed in Automatic mode0
Pre-selection for Automatic mode - This speed is active in Automatic mode (values between 0-3)

3.Outputs

No.NameInitialisationSBCDescription
1Speed 10s
Speed 1 (1 bit, 1 = switched on)
2Speed 20s
Speed 2 (1 bit, 1 = switched on)
3Speed 30s
Speed 3 (1 bit, 1 = switched on)
4Display of manual mode0s
Display in Manual mode (1 bit, 1 = Manual mode)
5Display of Automatic mode0s
Display in Automatic mode (1 bit, 1 = Automatic mode)
6Display blocked/Off0s
Display blocked/off (1 bit, 1 = blocked or fan off)
7Status (value)0s
Status (value)
Value 0 = Fan blocked, Speed 0=active
Value 1 = Fan released
Value 10 = Fan off
Value 11 = Manual mode/Speed 1 active
Value 12 = Manual mode/Speed 2 active
Value 13 = Manual mode/Speed 3 active
Value 14 = Automatic mode
8Speed value0s
Display speed value(1 byte)
0 = Fan off
1 = Speed 1
2 = Speed 2
3 = Speed 3
4 = Automatic mode
9Display of Manual/Automatic mode (1=Manual, 0=Automatic)0s
Display of Manual/Automatic mode (1=Manual, 0=Automatic)