1.Description
This module is used in conjunction with the DCS IP gateway (Gira Article No. 2620xx). Door opener commands from Gira Keyless In components can be evaluated and functions in the HS/FS or KNX/EIB can be run.
With the optional assignment of the Inputs 2 to 7, the arriving telegrams can be filtered with regard to the following properties:
- Bus addresses
- Keyless In device types
- Index numbers
- Near/far field (on Transponder readers)
- Sender type
This means that: With inputs set, only telegrams (with door opener commands) are evaluated which match the filter properties. Here it is irrelevant whether one or more inputs are assigned.
Examples:
With the bus address "0xABCDEF" set, only telegrams are evaluated which have been sent from the bus address "0xABCDEF".
By setting the Keyless In device type to the value "Transponder", all telegrams from transponder readers will be evaluated which contain a TC bus door opener command, regardless of the bus address, the index number or whether the door opener command has been triggered with a near/far field.
Examples:
With the bus address "0xABCDEF" set, only telegrams are evaluated which have been sent from the bus address "0xABCDEF".
By setting the Keyless In device type to the value "Transponder", all telegrams from transponder readers will be evaluated which contain a TC bus door opener command, regardless of the bus address, the index number or whether the door opener command has been triggered with a near/far field.
Note
If no filters are set, then all telegrams from TC bus switching actions are evaluated!
The module requires the firmware version of the DCS IP gateway 1.11 or higher!
Determination of the optional filter parameters
Two different methods are available for determining the filter parameters:
Two different methods are available for determining the filter parameters:
- Use of the HomeServer cheat sheet in the DCS IP gateway.
- Use of the logic node Display basic parameters in the "Door communication\Additional nodes" folder.
After the parameters are known, it is recommended that the inputs be assigned either group addresses or fixed values.
2.Inputs
No. | Name | Initialisation | Description |
---|---|---|---|
1 | Door communication Receive | "" | (14 bytes – Text) Here the internal communication object Door communication Receive is assigned by the DCS IP gateway. |
2 | Bus address | "" | (14 bytes – Text) Optional specification of a bus address to which filtering should be applied. The bus address must have the following format: Example: 0xABCD07 or 0x42A305 Note If this input remains free, the telegrams of random bus addresses are evaluated. If a communication object is assigned but is not written to or provided with an initialisation value, then the object is considered not to be set. This means the incoming telegrams of all bus addresses are evaluated. |
3 | Keyless In device type | 0 | (Value range 0 to 7) 1 = Transponder reader 2 = Fingerprint reader 3 = Code keypad |
4 | Index number | 0 | (Value range 0 to 255) Example: Finger 17, transponder card 22 Code keypad/Fingerprint reader Value 252: Sabotage contact of code keypad/fingerprint reader Value 253: F button pressed Value 254: Invalid index detected Value 255: Old Keyless In firmware |
5 | Near/far field (transponder only) | 2 | (Value range 0 to 1) 0 = far field 1 = near field |
6 | Sender type | 0 | Optional specification of a sender type to which filtering should be applied. The following parameters are possible: 160 = Door station 161 = Living area intercom 162 = Living area intercom receiver 163 = Bus control device 164 = Switching actuator 165 = TC gateway 166 = Additional gong/Bus chiming mechanism 167 = Button interface 168 = DCS IP gateway |
7 | Target address | "" | (14 bytes – Text) This input can be used from DCS IP gateway firmware version xxxxx. Optional specification of a target address to which filtering should be applied. The target address must have the following format here: Examples: 0xABCD07 or 0x42A305 Note If this input remains free, the telegrams of random bus addresses are evaluated. If a communication object is assigned but is not written to or provided with an initialisation value, then the object is considered not to be set. This means the incoming telegrams of all bus addresses are evaluated. |
8 | Release | 1 | This input enables the module to be blocked with regard to the telegram evaluation (e.g. for a time-controlled floor call function). Input value is not equal to 0 The module is completely calculated. Output 1 is calculated depending on the default values. Output 2 sends no telegram! Input value = 0 The module is not completely calculated. Output 2 is calculated depending on the default values. Output 1 sends no telegram! |
3.Outputs
No. | Name | Initialisation | SBC | Description |
---|---|---|---|---|
1 | Trigger - Module active | 0 | s | A 1 is sent on this output when the input telegram matches all filter properties. If filters are missing, then a 1 is sent each time a floor call telegram is received. For input telegrams which do not meet the filter criteria, the output sends a 0. |
2 | Trigger - Module inactive | 0 | s | In the case of a blocked module, the output sends a 1 when the input telegram complies with all filter properties. In the case of a blocked module, the output sends a 0 when the telegram does not comply with the filter properties. |
3 | Bus address | "" | s | (14 bytes – Text) Output of the bus address in the format: 0xABEF07 |
4 | Keyless In device type | 0 | s | (Value range 0 to 7) 1 = Transponder reader 2 = Fingerprint reader 3 = Code keypad |
5 | Index number | 0 | s | (Value range 0 to 255) Example: Finger 17 Value 252: Sabotage contact of code keypad/fingerprint 7 Value 253: F button pressed Value 254: Invalid index detected Value 255: Old Keyless In firmware |
6 | Near/far field (transponder only) | 0 | s | The output will be written exclusively with telegrams from a transponder reader dependent on any filters set. 0 = far field 1 = near field |
7 | Sender type | 0 | s | Device type from which the TC bus telegram has been sent. 160 = Door station 161 = Living area intercom 162 = Living area intercom receiver 163 = Bus control device 164 = Switching actuator 165 = TC gateway 166 = Additional gong/Bus chiming mechanism 167 = Button interface 168 = DCS IP gateway |
8 | Target address | "" | s | (14 bytes – Text) This output can be used from DCS IP gateway firmware version xxxxx. Output of the target address in the format: 0xABEF07 |
9 | Error output | 0 | s | The output can be routed to the outside as a diagnostic output if necessary or during start-up in order to obtain information about possible errors. Values in the value range 0 to 4 are sent. 0 = An error has not occurred. 1 = The default values must be checked. 2 = The characters of the bus or target address must be checked. 3 = A telegram with a different structure has been received (e.g. a light call). 4 = The logic is blocked. 5 = The default values for the near/far field defaults must be checked. 6 = Old firmware of the DCS IP gateway is present. |
s = send, sbc = send by change
4.Other
Recalculation during start: | No |
---|---|
Module is retentive: | No |
Internal designation: | 16917 |
Category: | Door communication\Receive |
5.Similar functions
Receive
Switching action
Floor call
Internal call
Door call (incl. bell symbol on code keypad)
Switching action Keyless In
Door opener command
Light function
Evaluation Sabotage KeyLessIn
Evaluate status automatic door opener DCS Communicator
Button event DCS Communicator
Button event home station/TC gateway
Evaluate voice message door station
Evaluate status of forwarding
Response - Evaluate status of JPEG image call
Evaluation of sabotage control device
Floor call
Internal call
Door call (incl. bell symbol on code keypad)
Switching action Keyless In
Door opener command
Light function
Evaluation Sabotage KeyLessIn
Evaluate status automatic door opener DCS Communicator
Button event DCS Communicator
Button event home station/TC gateway
Evaluate voice message door station
Evaluate status of forwarding
Response - Evaluate status of JPEG image call
Evaluation of sabotage control device
Receive\Evaluate code from code keypad
Universal filter function with code specification as text
Universal filter function with code specification as value
Universal filter function with code specification as value
Send
Light function
Switching action
Query/set automatic door opener DCS Client
Door station voice message
Query/set forwarding
Terminate call status of DCS bus devices
Switching action
Query/set automatic door opener DCS Client
Door station voice message
Query/set forwarding
Terminate call status of DCS bus devices
Additional modules