1.Description
This module forwards a telegram when the module is not locked-out. The commands are executed depending on the value of the output telegram. The module distinguishes between a value zero and a value not equal to zero of the input telegram. As many commands as desired can be assigned. If the value of the input telegram is not equal to zero, the assigned commands are executed. Data type and value of the input telegram are not changed. Example: Implementation of input telegrams at output telegrams with another group address.
2.Inputs
No. | Name | Initialisation | Description |
---|---|---|---|
1 | E1 (1=open) | 1 | Lock-out - This input controls the behaviour of the module. All telegrams are passed through if there is a value at the input that is not equal to zero. If there is a value 0 (zero), no telegrams are passed through. |
2 | E2 Signal | 0 | The communication objects whose values are to be forwarded are assigned here. |
3.Outputs
No. | Name | Initialisation | SBC | Description |
---|---|---|---|---|
1 | A1 | 0 | s | The received telegrams are output here. |
s = send, sbc = send by change
4.Other
Recalculation during start: | No |
---|---|
Module is retentive: | No |
Internal designation: | 9008 |
Category: | Lock-out |