Cooling
Contents

1.Description

Control module

2.Inputs

No.NameInitialisationDescription
1Setpoint Temp. (in °C)0
Setpoint (e.g. setpoint temperature in °C)
2Actual value (in °C)0
Actual value (e.g. actual temperature in °C)
3100% range0
Information on the size of the control range or 100 percent range in temperature units area (e.g. °C) in which variable control takes place.
The range within which control takes place is limited by "setpoint temperature" (lower limit, Input 1) and "setpoint temperature plus input value control range (value of this input)" (upper limit).
Note
The lower and upper limit do not belong to the range.
If the actual temperature lies above this range, the fixed correcting variable = 100%.
If the actual temperature lies within this range, the correcting variable is calculated.
If the actual temperature lies below this range, the fixed correcting variable = 0%.
See also the value table below.
4Factor (Initialisation==1)1
Control factor (minimum 1) The control factor influences the slope of the control curve in the control range, i.e., the time until the setpoint temperature is reached. Lower values lead to a flat control curve (longer duration). Higher values lead to a steep control curve (shorter duration).
5Cycle (sec.)0
Calculation cycle in seconds. A zero as cycle time deactivates the module (independently of the setting at Input 6).
The first calculation carried out by the module takes place after expiry of the first cycle.
A change of the cycle value or setting the lock-out (Input 6) to the zero value restarts the timer: The new cycle begins in this moment.
6Lock-out (1=blocked)0
Lock-out
- 0 = Controller working
- 1 = Controller is blocked.

If the lock-out is set to zero, this triggers a restart of the timer for the calculation cycle (Input 5): The new cycle begins in this moment.

3.Outputs

No.NameInitialisationSBCDescription
1Correcting variable0s
Correcting variable (0 to 100%)
2Correcting variable (sbc)0sbc
Correcting variable (0 to 100%)
3Number of cycles0s
Number of calculation cycles performed.
Note
This output is for further information. Assignment is not necessary for standard use.
s = send, sbc = send by change

3.1.Value table as an example

E1 - Target temp
(°C)
E2 - Actual temp
(°C)
E3 - Control range 100% (°C)E4 - FactorA1 - Correcting variable (%)Comment
2828310Actual temperature (28) = Setpoint temperature (28) = Lower limit (28): It is not cooled.
2827310Actual temperature lies below the setpoint temperature: : It is not cooled.
28293116.81The setpoint temperature being slightly exceeded leads to moderate cooling.
28293275.57A higher factor leads to a steeper control curve. This means that the setpoint temperature is reached quicker.
283131100Actual temperature (31) = Setpoint temperature (28) + Input value control range (3) = Upper limit (31): Maximum cooling
283231100Actual temperature (32) > Setpoint temperature (28) + Input value control range (3) = Upper limit (31): Maximum cooling
28325147.01Through the enlargement of the control range, 100% cooling is no longer set, even at 32 degrees.

4.Other

Recalculation during start:Yes
Module is retentive:No
Internal designation:9087
Category:Controller

5.Similar functions

Heating